Performonce of Fouling Fluidized-Removing and Heat Transfer Enhancement on Sewage Side of Sewage-Source Heat Pump System
Authors:BI Hai-yang and DUAN Mu-lin
Institution:Faculty of Mechanical Engineering, Materials Energy, Dalian 116024, Liaoning, P.R.China;Civil and Architectural Engineering College, Dalian University, Dalian 116622, Liaoning, P.R.China;Faculty of Infrastructure Engineering, Dalian University of Technology, Dalian 116024, Liaoning, P.R.China
Abstract:High thermal resistance resulted by fouling in heat exchanger restricts the application of sewage source heat pump (SSHP) system. The fouling forming mechanism was applied with solid-liquid fluidized bed technique for fouling prevention and removing of SSHP system. Shearing stress model of solid-liquid fluidized bed heat-exchanger is analyzed, and collision stress model is modified. Preventing and removing fouling mechanisms of solid-liquid fluidized bed technique by shearing stress and collision stress was explained. An experimental study on how to solve the fouling problem (such as fouling prevention and removing, heat transfer enhancement, etc) is discussed. The results of theory and experiment show that solid-liquid fluidized bed technique can be used not only to increase convection coefficient, but also to restrict fouling growing, it can effectively solve the fouling problem in SSHP system.
Keywords:sewage source heat pump  fouling fluidized-removing  heat transfer
点击此处可从《保鲜与加工》浏览原始摘要信息
点击此处可从《保鲜与加工》下载免费的PDF全文