Simulation of Evacuating Buffer in High-rise Building Fires |
| |
Authors: | He Jia-peng Li Jing-xian Zhou Ru and Xu Xiao-lei |
| |
Institution: | School of Urban Construction and Safety Engineering,Jiangsu Key Laboratory of Urban and Industrial Safety, Nanjing University of Technology,Nanjing 210009, P.R.China;School of Urban Construction and Safety Engineering,Jiangsu Key Laboratory of Urban and Industrial Safety, Nanjing University of Technology,Nanjing 210009, P.R.China;School of Urban Construction and Safety Engineering,Jiangsu Key Laboratory of Urban and Industrial Safety, Nanjing University of Technology,Nanjing 210009, P.R.China;School of Urban Construction and Safety Engineering,Jiangsu Key Laboratory of Urban and Industrial Safety, Nanjing University of Technology,Nanjing 210009, P.R.China |
| |
Abstract: | Buffer zone set between aisle and anteroom is proposed to improve the traditional mode of pressurizes mechanic smoke extraction. Fire Dynamic Simulation is used to simulate the model of high-rise fire. Eight models are set and analyzed, in which the smoke temperature distribution and concentration distribution are compared, and the best parameters is worked out. The result shows, when exhaust smoke volume is constant, the velocity of air curtain is as low as possible; when the volume of air curtain is constant, the smoke volume is as low as better. Based on the comparison, it is found that the smoke removal efficiency of mode 4 is the best one, which is about 74.06%. The evacuating buffer not only can let smoke out timely, but also can guarantee safe personnel evacuation. |
| |
Keywords: | high-rise building smoke control numerical simulation evacuating buffer |
|
| 点击此处可从《保鲜与加工》浏览原始摘要信息 |
| 点击此处可从《保鲜与加工》下载免费的PDF全文 |
|