首页 | 本学科首页   官方微博 | 高级检索  
     检索      

A Hilbert fractal antenna and portable monitoring system for partial discharge detection in gas insulated substations
引用本文:ZHANG Xiao xing,LIU Wang ting,YANG Xiao hua,ZUO Fei and HUANG Hu .A Hilbert fractal antenna and portable monitoring system for partial discharge detection in gas insulated substations[J].保鲜与加工,2009(3):263-268.
作者姓名:ZHANG Xiao xing  LIU Wang ting  YANG Xiao hua  ZUO Fei and HUANG Hu 
作者单位:State Key Laboratory of Power Transmission Equipment & System Security and New Technology, Chongqing University, Chongqing 400030, P. R. China;;State Key Laboratory of Power Transmission Equipment & System Security and New Technology, Chongqing University, Chongqing 400030, P. R. China;;Nan’an Power Supply Bureau, Chongqing Electric Power Company, Chongqing 400060, P. R. China);Nan’an Power Supply Bureau, Chongqing Electric Power Company, Chongqing 400061, P. R. China);Nan’an Power Supply Bureau, Chongqing Electric Power Company, Chongqing 400062, P. R. China)
摘    要:We design a third Hilbert fractal antenna for partial discharge (PD) monitoring in gas insulated substations (GIS) based on fractal principles, and analyze the Hilbert antenna impedance characteristics using an equivalent inductance method of parallel transmission lines. The PD experiment of metal protrusion defect is conducted employing fractal and microstrip antennae. The test results show that the characteristic of the Hilbert fractal antenna has good performance and can detect the PD signal for online monitoring in GIS. A portable online monitoring and locating system for GIS is established using the Hilbert fractal antenna and LabVIEW. The locating accuracy of the PD source in the laboratory meets the requirements of the PD site location.

关 键 词:gas  insulated  substation    partial  discharge    ultra  high  frequency  Hilbert  fractal  antenna
点击此处可从《保鲜与加工》浏览原始摘要信息
点击此处可从《保鲜与加工》下载免费的PDF全文
设为首页 | 免责声明 | 关于勤云 | 加入收藏