大型浮顶油罐防火间距的可行性论证
引用本文:韩钧.大型浮顶油罐防火间距的可行性论证[J].油气储运,2002,21(10):37-40.
作者姓名:韩钧
作者单位:中国石化工程建设公司
摘    要:对于大型浮顶油罐的防火间距,在介绍国外标准和做法的基础上,从安全,经济以及初中经验等方面论证了大型浮顶油罐20m防火间距的可行性,结论是GB50074-2002《石油库设计规范》第6.0.5条规定,浮顶油罐,内浮顶油罐之间的防火间距按0.4D计算大于20m时,最小可取20m,该规定兼顾了确定油罐间距所要考虑的四个主要因素(防火要求,消防操作要求,消防设施的能力和经济利益),符合安全可靠,经济合理的工程建设原则。

关 键 词:规范  大型浮顶油罐  防火间距  可行性  论证

Feasibility Demonstration on Spacing of Large-scale Floating Roof Oil Tank
HAN Jun.Feasibility Demonstration on Spacing of Large-scale Floating Roof Oil Tank[J].Oil & Gas Storage and Transportation,2002,21(10):37-40.
Authors:HAN Jun
Abstract:The feasibility demonstration on 20 m spacing for large-scale floating roof oil tank is made from safety ,economy and experiences. The conclusion can be seen in the clause 6. 0. 5 of GB50074-2002,which considers the four factors in determination tank spacing in fire control requirements extinguishment requirements , scope of fire control and economic prof its, meets the needs of safety, reliability and cost-effective principles in tank construction.
Keywords:floating roof oil tank  tank spacing  standard  feasibility  demonstration  