首页 | 本学科首页   官方微博 | 高级检索  
     检索      

Numerical Simulation of Dynamic Response of Suspension Insulator String
作者姓名:ZHENG Jia-yan  YAN Bo  LIU Xiao-hui  CHEN Zhi-  LIU Zhong-quan
作者单位:1. College of Resource and Environmental Science, Chongqing University, Chongqing 400030, China; 2. College of Engineering and Technology, Southwest University, Chongqing 400716, China; 3. Southwest Electric Power Design Institute,Chengdu 610021 ,China
摘    要:Finite element method is applied to analyze the windage of suspension insulator strings under dynamic wind loads. The dynamic response of a suspension insulator string of 500 kV high voltage transmission line is numerically simulated with ABAQUS software, and results demonstrate that the windage angle of suspension insulator string is larger than that calculated by the conventional design code, which might be one of the main reasons of the frequently happened windage flashover accidents.

关 键 词:high  voltage  transmission  line    insulator  string    dynamic  wind  loads    windage    finite  element  method
收稿时间:2006/6/18 0:00:00
修稿时间:2006/6/18 0:00:00

Numerical Simulation of Dynamic Response of Suspension Insulator String
ZHENG Jia-yan,YAN Bo,LIU Xiao-hui,CHEN Zhi-,LIU Zhong-quan.Numerical Simulation of Dynamic Response of Suspension Insulator String[J].Storage & Process,2006(12):100-103115.
Authors:ZHENG Jia-yan  YAN Bo  LIU Xiao-hui  CHEN Zhi-d  LIU Zhong-quan
Institution:1. College of Resource and Environmental Science, Chongqing University, Chongqing 400030, China; 2. College of Engineering and Technology, Southwest University, Chongqing 400716, China; 3. Southwest Electric Power Design Institute,Chengdu 610021 ,China
Abstract:Finite element method is applied to analyze the windage of suspension insulator strings under dynamic wind loads. The dynamic response of a suspension insulator string of 500 kV high voltage transmission line is numerically simulated with ABAQUS software, and results demonstrate that the windage angle of suspension insulator string is larger than that calculated by the conventional design code, which might be one of the main reasons of the frequently happened windage flashover accidents.
Keywords:high voltage transmission line  insulator string  dynamic wind loads  windage  finite element method
点击此处可从《保鲜与加工》浏览原始摘要信息