首页 | 本学科首页   官方微博 | 高级检索  
     

蜡沉积对流量计检定的影响
引用本文:丁华清,秦海洋. 蜡沉积对流量计检定的影响[J]. 油气储运, 2003, 22(12): 38-39,59
作者姓名:丁华清  秦海洋
作者单位:1. 中石化管道储运公司黄岛油库
2. 中石化管道储运公司潍坊输油处
摘    要:输油温度和环境温度的变化,导致原油中的蜡析出,用体积管检定容积式流量计时,由于蜡吸附,体积管基准管段标准容积减少,严重影响流量计检定结果。分析了蜡析出过程和析出条件,以实例说明体积管内壁结蜡对流量计检定结果和计量准确度的影响,提出了避免体积管结蜡应采取的措施。

关 键 词:蜡沉积 流量计 检定 量值传递 油品 输油温度

Analysis on the Influence of Wax Deposit to Flowmeter Proving
DING Huaqing and QIN Haiyang. Analysis on the Influence of Wax Deposit to Flowmeter Proving[J]. Oil & Gas Storage and Transportation, 2003, 22(12): 38-39,59
Authors:DING Huaqing and QIN Haiyang
Affiliation:DING Huaqing and QIN Haiyang
Abstract:The change of temperature of oil transported and ambient temperature result in t he wax deposit, whichdecreases the standard volume of pipe-type meter prover and proving precision of flowmeter. This paper analyzes the process and condition of wax deposit,describ es the influence of wax d eposit on the internal wall of pipe-type meter to proving result and accuracy of flowmeter and gives the mea sures to be taken to avoid the wax deposit of pipe-type meter.
Keywords:flowmeter   proving   wax deposit   influence   analysis