首页 | 本学科首页   官方微博 | 高级检索  
     检索      

冰蓄冷中央空调预热泵流量模糊控制
引用本文:徐今强,冯自平,肖睿,黄冲.冰蓄冷中央空调预热泵流量模糊控制[J].排灌机械,2010,28(3):260-264.
作者姓名:徐今强  冯自平  肖睿  黄冲
作者单位:1. 中国科学院,广州能源研究所,广东,广州,510640;中国科学院,研究生院,北京,100049;广东海洋大学,海洋遥感与信息技术实验室,广东,湛江,524088
2. 中国科学院,广州能源研究所,广东,广州,510640
基金项目:国家自然科学基金委-广东省联合基金资助项目,国家863计划项目 
摘    要:为了解决冰蓄冷中央空调存在的板换堵塞问题,提出了以制冰板换回水温度为控制变量,采用模糊控制预热变频泵流量的方法,以实现制冰快速性和可靠性的解决方案.设计了预热泵流量模糊控制器,研制了制冰板换防堵塞的预热回路;采用离线计算与在线查询相结合的方法,对基于西门子可编程逻辑控制器(PLC)的冰蓄冷中央空调系统进行了试验研究,给出了制冰板换回水温度控制结果,并对该模糊控制结果与传统的PID控制结果进行了比较.试验结果表明:在环境温度为28℃时,采用模糊控制调节制冰板换回水温度,其下降时间为90 m in,调节时间为158 min,稳态误差为0.26℃.该方案为智能化冰蓄冷中央空调稳定运行提供了依据.

关 键 词:冰蓄冷空调  流量  温度  模糊控制  可编程逻辑控制器

Fuzzy control of pre-heat pump flow in ice-storage centralized air-conditioning
Xu Jinqiang,Feng Ziping,Xiao Rui,Huang Chong.Fuzzy control of pre-heat pump flow in ice-storage centralized air-conditioning[J].Drainage and Irrigation Machinery,2010,28(3):260-264.
Authors:Xu Jinqiang  Feng Ziping  Xiao Rui  Huang Chong
Institution:1.Guangzhou Institute of Energy Conversion,Chinese Academy of Sciences,Guangzhou,Guangdong 510640,China;2.Graduate University of Chinese Academy of Sciences,Beijing 100049,China;3.Ocean Remote Sensing and Information Technology Laboratory,Guangdong Ocean University,Zhanjiang,Guangdong 524088,China)
Abstract:The plate heat exchanger of ice-storage centralized air-conditioning system is always jammed.With the objective of making ice quickly and reliably,a solve scheme was proposed.With consideration of the return water temperature of ice-making plate heat exchanger as controlled variable,the scheme regulated the flow rate of pre-heat pump by means of fuzzy control.A fuzzy controller was designed to dominate the flow rate of the pump,and a pre-heat loop was developed to prevent the ice-making plate heat exchanger from jamming.The experimental investigation of Siemens PLC based ice-storage centralized air-conditioning was performed by combining offline calculation with online inquiry,and the control effect of return water temperature of ice-making plate heat exchanger was compared with the traditional PID control.The results show that when the environmental temperature is 28 ℃,the fall time,the settling time and the steady state error of return water temperature are 90 min,158 min and 0.26 ℃,respectively.The scheme provides the basis for stable operation of the intelligent ice-storage centralized air conditioning system.
Keywords:ice-storage air-conditioning  flow rate  temperature  fuzzy control  programmable logic controller
本文献已被 维普 万方数据 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号